Table 4-2. Unit Maintenance Troubleshooting
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. AIR CONDITIONER DOES NOT START IN ANY MODE.
Step 1. Check to see if input power has been disconnected.
Connect input' power.
Step 2. Make sure that power is 208 volt; 3 phase, 50/60 hertz.
Connect correct input power.
Step 3. Check to see if compressor circuit breaker is tripp ed.
Slowly PULL AND PUSH TO RESET CIRCUIT BREAKER.
Step 4. Check for loose or damaged electrical connectors or damaged wires in wiring harnesses.
(See para 4-54.)
Tighten or replace connectors, or repair damaged wires.
Step 5. Check op eration of Circuit Breaker (CB).
Test Circuit Breaker (CB). (See para 4-42). Replace circuit breaker if defective.
Step 6. Check operation of control power transformer (T).
Test transformer. (See para 4-49.) Replace transformer if defective.
Step 7. Check operation of RFI filters (FL1 thru 4) and dc rectifier assembly (CR).
Step 8. Check all terminals and internal wiring in junction boxes for tightness and damage.
Step 9. Check operation of mode selector switch (S).
Test switch. (See para 4-38). Replace switch if defective.