TM 5-4120-393-14
Table 4-2. Unit Maintenance Troubleshooting
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
b. Test switch in TEMPerature control thermostat. (See para 4-37.) Replace entire
control if defective.
Step 4.
Check operation of mode selector switch (S).
Test switch. (See para 4-38.) Replace switch if defective.
11. REDUCED HEATING CAPACITY.
Step 1.
Check airflow out of conditioned air (evaporator) discharge grille. If airflow volume is low:
a. Adjust conditioned air (evaporator) intake grille louvers.
b. Clean and service, or replace, conditioned air filters. (See para 4-30.)
c. Clean and service, or replace, mist eliminator. (See para 4-32.)
d. Clean evaporator coil and entire evaporator section. (See para 4-62.)
Step 2.
Check adjustment of fresh air damper and/or CBR filter, if installed
Adjust properly.
Step 3.
Check operation of heater thermostat (S3).
WARNING
Disconnect input power before performing internal electrical troubleshooting.
Voltages used can be deadly.
Test thermostat. (See para 4-57.) Replace thermostat if defective.
Step 4.
Check operation of individual heater elements (HR1, 2, 3, 4, 5, 6).
Test each element. (See para 4-58.) Replace defective elements.
Step 5.
Check operation of TE MPerature control thermostat (S1).
a. Inspect sensing bulb and capillary for damage or leakage. Replace entire control if bulb
is damaged or leaking.
b. Test switch in TEMPerature control thermostat (S1). (See para 4-37.) Replace entire
control if defective.