4120-01-238-4277">
|
|
TM 5-4120-393-14
4-36.
Control Panel Wiring Harness and Electrical Leads
This task covers:
a. Removal
c. Repair
b. Inspection
d. Installation
Initial setup.
Tools:
Tool kit, service, refrigeration unit NSN 5180-00-596-1474.
Multimeter NSN 6625-00-553-0142
Personnel:
1
Equipment condition:
1. Turn unit power off at power source. If there is a chance that it will be turned on, also disconnect power cable to
air conditioner.
2. Remove control panel. See para 4-35.
General Safety Instructions:
WARNING
Disconnect input power to the air conditioner before performing any internal
maintenance. Voltages used can KILL. Shutting the unit off at the control panel
does not disconnect unit power.
REMOVAL
1.
Using allen wrench, loosen TEMPerature control thermostat knob (1) setscrew (2).
2.
Remove knob (1).
3.
Using screwdriver and wrench, remove four screws (3) and nuts (4) that secure rear panel (5).
4.
Pull rear panel (5) away from box (6) as far as harness will allow.
NOTE
Inspection (installed) can be done at this point.
5.
Using screwdriver and wrench, remove four screws (7) and nuts (8) from J8 connector (9).
6.
Tag and disconnect leads from switches.
7.
Remove grounding screw (10), lock nut (11), two lock washers (12), four flat washers (13), and nut (14).
8.
Remove harness (15).
9.
Remove bevelled spacer (16) from harness (15).
4-84
|