5-16. Dehydrator (Filter-Drier) (cont)
INSTALLATION
CAUTION
Replacement dehydrators are packed with sealing caps on the flare fittings to
prevent moisture contamination of the desiccant filtering media. Remove these
caps immediately prior to installation. Never install a dehydrator from which caps
have been removed for an extended or unknown period of time.
1.
Place clamp (3) on dehydrator (5).
2.
Place clamp (3) and dehydrator (5) in unit. Be sure that flow ar row is pointing down.
3.
Using screwdriver, secure clamp (3) with screw (1) and nut (2).
4.
Using wrench, tighten both flare nuts (4).
5.
Leak test all newly connected joints and those in the repair area. See para 5-12.
6.
NOTE
FOLLOW ON MAINTENANCE:
1. Install junction box number two. See para 4-46.
2. Install lower front panel. See para 4-24.
3. Connect power.
5-37
|