TM9 4120-423-14&P
9
Turn selector switch to LOW HEAT.
10
Turn temperature control to maximum WARMER.
11
Using multimeter, check temperature control output voltage between terminals CR1-4 neg (-)
and A1K1-5. Voltage should be 25 to 31 Vdc.
12
Turn selector switch to OFF.
13
Remove power to air conditioner.
END OF TASK
0035 00-5
|