Click here to make tpub.com your Home Page

Page Title: ADJUSTMENT
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM9 4120-423-14&P
4
Using screwdriver, secure valve to bracket with a screw, lockwasher, and clamp.
5
Replace the dehydrator. (See WP0080).
6
Leak test all newly connected joints and those in the repair area. (See WP0073).
7
Evacuate and charge the Refrigerant R-22 system. (See WP0074 and WP0075).
8
Install right end condenser cover. (See WP0045).
9
Install condenser section electrical module assembly. (See WP0051.)
10
Install air conditioner on shelter. (See WP0006).
11
Connect power.
ADJUSTMENT
1
Valves are factory set to start opening when suction pressure decreases to 58 psig. Do not adjust
unless you are sure adjustment is necessary.
2
Using screwdriver, remove eight screws from condenser section electrical module assembly.
3
Pull module out and to side. Do not disconnect P12 and P13 connectors.
4
Operate air conditioner in COOL mode with temperature control in maximum WARMER
position and pressure gauge connected to LOW SIDE service valve (compressor suction).
5
Bypass valve should open when LOW SIDE pressure drops to between 52 and 60 psig.
6
To adjust, use hand to remove cap covering adjusting screw in bypass valve.
7
Use 5/16 inch Allen wrench to turn adjusting screw to raise or lower bypass valve opening
pressure. Adjust slowly.
8
Replace cap.
9
Turn off air conditioner and disconnect power.
END OF TASK
0083 00-3

Privacy Statement - Press Release - Copyright Information. - Contact Us