Click here to make tpub.com your Home Page

Page Title: MALFUNCTION/SYMPTOM
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 9-4120-425-14&P
OPERATOR MALFUNCTION/SYMPTOM INDEX
TROUBLESHOOTING
MALFUNCTION/SYMPTOM
PROCEDURE
Air Conditioner Fails to Operate
1.
Power cable not connected to proper voltage and phase or proper connector (J2 or
J1 ALTERNATE).
2.
Circuit breaker is OFF.
3.
Mode selector switch is in OFF position.
4. High pressure switch has not been reset.
Insufficient Cooling
1.
Mode selector switch is not properly positioned on COOL.
2.
Temperature switch is not set correctly to COOLER.
3.
Insufficient air is passing across the evaporator coil due to intake and discharge
louver obstructions.
4.
Too much outside air is entering the unit through the damper door.
5.
Insufficient refrigerant in the system.
6.
Insufficient air is passing through the condenser coil due to inlet and outlet
louver obstructions.
No Heat or Low Heat
1.
Temperature selector switch is not set correctly to WARMER setting.
2.
Insufficient air is passing over heaters due to obstructions of evaporator air intake
and discharge louvers.
3.
Insufficient air is passing over heaters due to evaporator air intake louver blades
being closed.
NOTE
Report fault to unit maintenance personnel if any of the following conditions occurs.
Compressor Will Not Start
1.
High-or-low pressure cut-out switch may have an open contact.
2.
Possible loose electrical connections or faulty wiring.
0009-00-1

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business