OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES - Continued
0011-00
Table 1. Operator Preventive Maintenance Checks and Services (PMCS) - Continued
ITEM TO BE
EQUIPMENT NOT
ITEM
CHECKED OR
READY/AVAILABLE
NO.
INTERVAL
SERVICED
PROCEDURE
IF:
11
During
Liquid Sight Indicator
After approximately 5 minutes in
Moisture or low charge
"COOL" mode operation, check for
is indicated.
moisture and low refrigerant charge.
Yellow indicates moisture; bubbles or
milky appearance indicates low charge.
Report abnormal condition to Direct
Support Maintenance personnel.
0011-00-3