OPERATOR MAINTENANCE INSTRUCTIONS
THIS WORK PACKAGE COVERS:
Service and Cleaning of Screens and Guards,
Adjusting Louvers, Damper and Control Module
INITIAL SETUP:
Maintenance Level
Operator
Materials/Parts
Dry Cleaning Solvent
(Item 16, WP 0121-00)
Brush
Cleaning Cloth (Item 9, WP 0121-00)
WARNING
Disconnect the power source before performing any maintenance function.
WARNING
Do not use compressed air for cleaning purposes except where reduced to less than
30 psi (2.1 kg/cm2) and then only with effective chip guarding and personnel
protective equipment.
WARNING
Dry cleaning solvent (WP 0121-00) used to clean parts is potentially dangerous to
personnel and property. Avoid repeated and prolonged skin contact. Do not use near
open flame or excessive heat. Flash point of solvent is 100F (38C).
SERVICE AND CLEANING
Screens and Guards
1.
Brush off any loose dirt or foreign matter, and remove obstructions from the condenser guard & fresh air screen.
2.
Wipe off with a cloth moistened with dry cleaning solvent (WP 0121-00).
3.
Inspect for security of attachment and damage.
4.
Report damaged condition to unit maintenance personnel.