TM 9-4120-425-14&P
UNIT PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS) - Continued
0016-00
"Interval" Column. Weekly and quarterly intervals are shown opposite the appropriate check. A weekly check is
performed weekly, If the check is accomplished quarterly, it is shown as a quarterly interval.
Table 1. Unit Preventive Maintenance Checks and Services (PMCS)
ITEM TO BE
EQUIPMENT NOT
ITEM
INTERVAL
CHECKED OR
PROCEDURE
READY/AVAILABLE
NO.
SERVICED
IF:
1
Weekly
Evaporator Air Intake
1.
Remove screw (1), washers (2) and
Items are damaged,
Filter and Evaporator
(3) to release evaporator air intake
missing or clogged.
Air Intake Louver
louver from unit. Remove air filter
(5) from clip inside louver casing.
WARNING
Dry cleaning solvent (Item 16, WP
potentially dangerous to personnel
and property. Avoid repeated and
prolonged skin contact. Do not use
near flame or excessive heat. Flash
point of solvent is 100F (38C).
2.
Inspect air filter (5) for damage.
Replace if damaged.
3.
Clean air filter (5) with mild soap
and water solution.
4.
Inspect louver (4) for bent blades.
Straighten or replace.
5.
Lubricate air filter (5) with filter-kote
(Item 17, WP 0121-00). Drain off
excessive oil.