TM 9-4120-425-14&P
UNIT PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS) - Continued
0016-00
Table 1. Unit Preventive Maintenance Checks and Services (PMCS) - Continued
ITEM TO BE
EQUIPMENT NOT
ITEM
INTERVAL
CHECKED OR
PROCEDURE
READY/AVAILABLE
NO.
SERVICED
IF:
4
Quarterly
Evaporator and
1.
Remove covers. See WP 0019-00.
Items are loose or
Condenser Fans and
damaged.
Motors
2.
Inspect evaporator motor (1),
condenser motors (2) and impellers
(3) and (4) for security of attachment,
rubbing and free turning.
3.
Check wiring for damage.
4.
Replace damaged impellers (3) or (4)
or motors (1 & 2) (WP 0033-00).
0016-00-4
|