DIRECT SUPPORT TROUBLESHOOTING PROCEDURES
THIS WORKPACKAGE COVERS:
Compressor Will Not Start, Compressor Starts But Stops At Once, Insufficient Cooling, Compressor
Runs But Does Not Cool, Compressor Excessively Noisy, Suction Pressure Too Low or Too High,
Low Heat or No Heat
INITIAL SETUP:
Maintenance Level
Direct Support
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, WP 0118-00)
Tool Kit, Service, Refrigeration Unit (Item 2, WP 0118-00)
Recovery and Recycle Unit, Refrigerant (Item 5, WP 0118-00)
Mask, Air Filtering (Item 29, Table 1, WP 0121-00)
Test Equipment:
Electronic refrigerant gas leak detector
References
Schematic Diagrams WP 0122-00
Equipment Condition
Mode selector switch in OFF position.
Main power source is disconnected.
Panels removed (WP 0019-00).
WARNING
Disconnect air conditioner power supply.
Table 1. Troubleshooting Procedures
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
COMPRESSOR WILL NOT
1.
Make continuity check of control
1.
Repair loose or broken
START
circuit and components. See WP
connections.
0122-00 for control circuit
schematic diagram. (Refer to WP
2.
Replace bad components. (Refer
2.
If fans do not operate, make
Replace bad circuit breaker. (Refer to
continuity check of circuit
breaker. (Refer to WP 0033-00.)
0047-00-1