|
|
TM 9-4120-425-14&P
REFRIGERATION SYSTEM DESCRIPTION
Description
WARNING
Unit contains R-22, a chemical substance which harms public health and the
environment by destroying ozone in the upper atmosphere, and that the equipment is
to be serviced by qualified personnel only.
WARNING
Whenever it is necessary to open the refrigeration system for any reason, discharge
the refrigerant carefully. Avoid contact with liquid refrigerant. As a minimum, all
personnel must wear thermal protective gloves, a face shield or goggles and a air
filtering mask when working in any situation to avoid R-22 contact with the skin or
eyes. Severe freezing of body tissues can take place with extreme rapidity. Avoid
excessive inhalation of refrigerant gas and ventilate the area in which it is released.
Refrigerant gas in contact with flame or hot surfaces is converted to phosgene a
highly toxic gas having an odor similar to newly mown grass or hay.
1.
The refrigeration system illustrated by the refrigerant flow diagram is a mechanical, vapor-cycle circuit consisting of
the evaporator thermal expansion valve, compressor, condenser, and the necessary valves and cutout devices for
automatic control during operation and servicing.
2.
The thermal expansion valve releases high-pressure liquid refrigerant into the evaporator at reduced pressure.
3.
The liquid refrigerant begins to vaporize by absorbing heat from the air passing over the outside surface of the
evaporator coil.
4.
The heated vapor is sucked out of the evaporator section by the compressor, and is forced into the condenser section
under high pressure where it is cooled and condensed back into a liquid.
5.
The heat released during condensation is carried off by the condensing airstream.
6.
The liquid refrigerant flows from the condenser to a filter-drier, sight glass and then to the thermal expansion valve
to repeat the cycle.
7.
If the temperature control (evaporator return-air thermostat) becomes satisfied (the evaporator return-air temperature
is lower than the point at which you have set the control) the refrigeration system will go into "Standby
Refrigeration Operating Condition" (no effective cooling but compressor remains operating).
8.
When the temperature control again calls for cooling (the evaporator return air temperature is higher than the point
at which the control is set) the refrigeration system will come out of the "Standby Refrigeration Operation
Condition" to "Full Refrigeration Operating Condition"(full cooling operation). If the system was shut-off (for any
reason) the equalization solenoid valve (15) will open equalizing the system pressure and a time delay of one-
minute will be encountered before compressor will restart.
Refrigeration System Repair
1.
The following paragraphs cover repairs of commonly used hardware, tubing and valves of the refrigeration system.
Re-use or repair of seals and gaskets should not be attempted; new parts should be used at assembly. When heating
refrigeration piping to debraze or unsolder connections (See Work Package WP 0051-00) as well as to solder or
braze them, the piping should be protected with a continuous flow of dry nitrogen to prevent scaling or oxidation of
the inside surface.
0048-00-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |