TM 9-4120-425-14&P
REFRIGERATION SYSTEM SERVICING (PURGING)
THIS WORK PACKAGE COVERS:
Service (Purging)
INITIAL SETUP:
Maintenance Level
Direct Support
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0118-00)
Tool Kit, Service, Refrigeration Unit (Item 2, Table 2, WP 0118-00)
Nitrogen Pressure Regulator (Item 4, Table 2, WP 0118-00)
Mask, Air Filtering (Item 29, Table 1, WP 0121-00)
Materials/Parts
Nitrogen (Item 4, WP 0121-00)
References
WP 0118-00 (MAC)
Equipment Condition
Refrigerant system discharged (WP 0049-00).
Main power source disconnected.
WARNING
Disconnect air conditioner power supply.
WARNING
Be sure that the manifold hoses are correctly connected. BLUE Hose = Low
Pressure, RED Hose = High Pressure.
WARNING
The refrigeration system must be purged with dry nitrogen, during any brazing
operation performed on any component. A flow of dry nitrogen at the rate of less
than 1 - 2 cfm (0.028-0.057 m3/minute) should be continued during all brazing
operations to minimize internal oxidation and scaling.
CAUTION
Nitrogen cylinders are pressurized containers. The pressure in the cylinder can
exceed 2000 PSI. A nitrogen pressure regulator must be used at all times when
nitrogen is used for leak check or purge operations.