REFRIGERATION SYSTEM SERVICING (PRESSURE TESTING) - Continued
0055-00
SERVICE PRESSURE TESTING - Continued
Refrigeration System Pressure Testing Continued
5.
Start air conditioner. With the unit operating, allow gauges to stabilize. Take reading of the two gauges.
6.
Compare gauge readings with the normal range of system pressure as shown on the Table of Normal Temperature
Pressure Relationships.
7.
Disconnect gauges.
8.
Install service valve access cover with screws.
Table 1. Normal Temperature - Pressure Relationships
Temperatures
Pressure Range (PSIG)
Outdoor Ambient
50F
75F
l00F
120F
Evaporator Intake
(10C)
(24C)
(38C)
(52C)
90F (32C)
55-65 Suction 150-
66-76 Suction 200-
76-86 Suction 280-
95-100 Suction 390-
Air to Unit (Dry
180 Discharge
240 Discharge
325 Discharge
428 Discharge
Bulb)
80F (27C)
50-60 Suction 140-
61-71 Suction 190-
71-81 Suction 270-
80-90 Suction 360-
Air to Unit (Dry
170 Discharge
230 Discharge
315 Discharge
410 Discharge
Bulb)
END OF TASK
0055-00-2
|