CONDENSATE DRAIN ASSEMBLY DIRECT SUPPORT MAINTENANCE
THIS WORK PACKAGE COVERS:
Removal, Disassembly, Cleaning, Repair and Installation
INITIAL SETUP:
Maintenance Level
Direct Support
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0118-00)
Equipment Condition
Air conditioner shut down and cool.
Front top cover removed (WP 0019-00).
Evaporator louvers removed (WP 0020-00).
Evaporator fan assembly removed (WP 0057-00).
Condenser fan scroll nearest condensate drain assembly removed (WP 0062-00).
Materials/Parts
Water, warm soapy
Wire, soft 10-12 gage
Bleach and water solution, mild
References
WP 0029-00 (Condensate Drain Assembly Unit Maintenance)
WARNING
Disconnect air conditioner power.
REMOVAL AND DISASSEMBLY
1.
Loosen clamps (1) and (3).
2.
Remove tubing (2) and (4).
3.
Refer to Unit Maintenance WP 0029-00 for maintenance of items (6).
CLEANING
1.
Clean tubing using warm soapy water or replace. Rinse with mild solution of bleach and water. Replace tubing if
defective.
2.
Clear obstructions from drains at bottom of evaporator compartment using soft wire. Rinse area with bleach
solution.
3.
Clear obstructions from drain outlet using soft wire. Insert wire from evaporator drain opening.
0056-00-1