EVAPORATOR FAN ASSEMBLY DIRECT SUPPORT MAINTENANCE - Continued
0057-00
REMOVAL - Continued
6.
Using a No. 3 screwdriver remove four screws (11) holding evaporator fan assembly (12) to cabinet.
7.
Angle assembly to the left to remove evaporator fan assembly (12) from unit.
REPAIR
Repair is limited to replacement of defective parts.
INSTALLATION
1.
Place evaporator fan assembly (12) into unit.
2.
Using No.3 screwdriver install four screws (11) to attach the evaporator fan assembly (12) to cabinet.
3.
Install two scroll ducts (10), four lock washers (9), and four screws (8).
4.
Using a cross tip screwdriver (Item 12, Table 2, WP 0118-00), install two nuts (7), two flat washers (6), and two
screws (5).
5.
Install electronic sensor (4), with clamp (3), lock washer (2), and screw (1) onto evaporator fan assembly (12)
frame.
6.
Connect two evaporator fan wires to terminal board TB2 in the remote control unit and remove tags. Connect
ground wire.
7.
Install heating elements. See WP 0027-00.
8.
Install evaporator air intake louver. See WP 0020-00.
9.
Install remote control module. See WP 0034-00.
10. Reassemble junction box support bracket. Refer to WP 0035-00.
11. Reconnect drain hoses (WP 0029-00).
12. Reconnect air conditioner to power source.
0057-00-2