TM 9-4120-425-14&P
FILTER-DRIER DIRECT SUPPORT MAINTENANCE REPLACEMENT - Continued
0066-00
FILTER-DRIER LOCATION
The filter-drier is located on the top center wall of the housing.
REMOVAL
WARNING
Check that power source is disconnected. Check that refrigerant system is discharged.
1.
Unscrew flare nuts (2) and remove refrigerant lines (5) from filter-drier (1).
2.
Remove screw (3) and strap (4).
3.
Remove filter-drier (1).
INSTALLATION
CAUTION
Replacement filter-drier are packaged with sealing caps on the flare fittings to
prevent moisture contamination of the desiccant filtering media. Remove these caps
immediately prior to installation. Never install a filter-drier from which caps have
been removed for an extended or unknown period of time.
1.
Check the direction arrow marked on the filter-drier (1).
2.
Position filter-drier (1) between refrigerant lines (5).
3.
Tighten flare nuts (2).
4.
Install strap (4) with screw (3).
5.
Leak test refrigerant system (See WP 0052-00).