|
|
TM 9-4120-425-14&P
SOLENOID VALVES AND HOT GAS BY-PASS VALVE
DIRECT SUPPORT MAINTENANCE REPLACEMENT Continued
0067-00
SOLENOID VALVES AND HOT GAS BY-PASS VALVE
TEST
Equalization Solenoid Valve (3)
NOTE
This is a test for valve operation and the equalization of discharge and suction
refrigerant pressure when compressor is shut off. When compressor is operating,
valve should be energized and closed. This is a normally open valve.
1.
Connect service gauges to service valves and observe pressures with system operating in the "cooling mode"with
unit delivering cold air.
2.
Turn selector switch to "OFF" and observe system refrigerant pressures.
3.
Refrigerant pressures (suction and discharge) should equalize immediately and be at same pressure within 5
seconds.
4.
Remove top rear panel (See WP 0019-00) and operate unit in "cooling mode" with unit delivering cold air for no
more than 2 minutes at a time.
5.
Observe temperature (by touch) of valve outlet tubing.
6.
Tubing temperature at valve outlet should be at approximately room temperature (NOT HOT).
7.
With unit operating as in step 4, and if tubing temperature in step 6 is hot, check solenoid coil by removing the
solenoid coil to feel the magnetic attraction of the coil to the valve.
8.
If there is no magnetic attraction of coil to valve, the problem is electrical and not the solenoid valve.
9.
If observation in step 3 and step 6 are not as stated, solenoid valve is defective and must be replaced.
Liquid Line Solenoid Valve (1)
NOTE
This is a test for valve operation. The valve functions in "cooling mode" to control
cooling output of unit by supplying liquid refrigerant to the cooling coil
(evaporator).
1.
Operate the unit in "cooling mode" and observe (evaporator) supply air temperature.
2.
With temperature selector in "coolest" position the supply air temperature should be cold (approximately 15F
below ambient).
3.
With the temperature selector in "warmest" position, the supply air temperature should be same as ambient
temperature or 1 or 2 degrees warmer.
4.
When the unit is operating as in step 2 above, but with supply air temperature not cold, remove top rear panel (See
WP 0019-00) and check solenoid coil by removing the solenoid coil to feel the magnetic attraction of the coil to the
valve.
0067-00-2
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |