|
|
TM 9-4120-425-14&P
SOLENOID VALVES AND HOT GAS BY-PASS VALVE
DIRECT SUPPORT MAINTENANCE REPLACEMENT
THIS WORK PACKAGE COVERS:
Test, Removal, and Installation
INITIAL SETUP:
Maintenance Level
Direct Support
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0118-00)
Tool Kit, Service, Refrigeration Unit (Item 2, Table 2, WP 0118-00)
Recovery and Recycle Unit, Refrigerant, (Item 5, Table 2, WP 0118-00)
Mask, Air Filtering (Item 29, Table 1, WP 0121-00)
References
WP 0118-00 (MAC)
Equipment Condition
Mode selector switch in OFF position.
Main power source is disconnected.
Top rear panel removed (WP 0019-00).
Condenser fan motor nearest hot gas by-pass valve removed (See WP 0031-00).
Condenser fan scroll and bracket nearest hot gas by-pass valve removed (See WP 0062-00).
Recover refrigerant from system (See WP 0049-00).
System purged with nitrogen (See WP 0050-00).
Debraze related tube connections (See WP 0079-00 and WP 0051-00).
Test Equipment
Electronic refrigerant gas leak detector
Materials/Parts
Nitrogen (Item 4, Table 1, WP 0121-00)
Brazing alloy (Item 5 or 6, Table 1, WP 0121-00)
Brazing flux (Item 7, Table 1, WP 0121-00)
Special Environmental Condition
NOTE
In accordance with Environmental Protection Agency regulations, refrigerants
cannot be discharged into the atmosphere. A refrigerant recovery and recycling unit
must be used whenever discharging the refrigerant system.
Operation of the recovery/recycling unit must be by AUTHORIZED PERSONNEL
ONLY.
0067-00-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |