TM 9-4120-425-14&P
TUBING AND FITTINGS DIRECT SUPPORT MAINTENANCE REPLACEMENT
THIS WORK PACKAGE COVERS:
Test, Removal and Installation
INITIAL SETUP:
Maintenance Level
Direct Support
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0118-00)
Tool Kit, Service, Refrigeration Unit (Item 2, Table 2, WP 0118-00)
Recovery and Recycle Unit, Refrigerant (Item 5, Table 2, WP 0118-00)
Mask, Air Filtering (Item 29, Table 1, WP 0121-00)
References
WP 0118-00 (MAC)
Equipment Condition
Mode selector switch in OFF position.
Main power source is disconnected.
Top covers removed (WP 0019-00).
Test Equipment
Electronic refrigerant gas leak detector
Materials/Parts
Nitrogen (Item 4, Table 1, WP 0121-00)
Brazing alloy (Item 5 or 6, Table 1, WP 0121-00)
Brazing flux (Item7, Table 1, WP 0121-00)
Special Environmental Condition
NOTE
In accordance with Environmental Protection Agency regulations, refrigerants
cannot be discharged into the atmosphere. A refrigerant recovery and recycling unit
must be used whenever discharging the refrigerant system.
Operation of the recovery/recycling unit must be by AUTHORIZED PERSONNEL
ONLY.
WARNING
Disconnect air conditioner power supply.
WARNING
Avoid bodily contact with liquid refrigerant and avoid inhaling refrigerant gas. Be
especially careful that refrigerant does not come in contact with eyes. In case of
refrigerant leaks, ventilate area immediately.