TM 9-4120-425-14&P
COIL (SOLENOID VALVE)
THIS WORK PACKAGE COVERS:
Test, Removal, and Installation
INITIAL SETUP:
Maintenance Level
Unit
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0118-00)
References
Schematic Diagram, WP 0122-00
Test Equipment
Multimeter
Equipment Condition
Air conditioner shut down and cool.
Power disconnected from unit.
Rear top cover removed (WP 0018-00 and WP 0019-00).
WARNING
Disconnect air conditioner power supply.
TEST
1.
Using multimeter set on the lowest OHMS scale, check for continuity between leads of coil. If continuity is not
found, coil is open and must be replaced.
2.
Using multimeter set on lowest OHMS scale, check for continuity between each lead and coil casing. If continuity is
found between either lead and the casing, the coil is grounded and must be replaced.
REMOVAL
1.
Tag and disconnect wires connected to solenoid valves (1) and (4).
2.
Remove spring clips (3) and (6) and coils (2) and (5).
INSTALLATION
1.
Install coils (2) and (5), with spring clips (3) and (6) onto solenoid valves (1) and (4).
2.
Refer to wire tags installed during removal and reconnect wires of coil as indicated and then remove tags.
3.
Install rear top cover. See WP 0018-00 and WP 0019-00.
4.
Reconnect air conditioner to power source.
0039-00-1
|