TM 9-4120-428-14
0090 00
9
9
1
10
2
1
11
2
4
3
KECO INDUSTRIES
WELCO INDUSTRIES
3 PHASE COMPRESSOR
COMPRESSORS
REMOVAL
1. Remove the dehydrator (WP 0075 00).
2. Purge the refrigerant system (WP 0066 00).
3. De-braze the compressor tubes (WP 0067 00).
4. Lift and support the air conditioner to gain access to the bottom of the housing.
5. Loosen four access panel screws (1) in the bottom of the unit and swing the access panels (2) out of the way.
6. Remove four self-locking nuts (3), eight flat washers (4), eight shims (5), and four screws (6).
WARNING
If compressor is removed due to burnout, avoid touching the compressor sludge when
lifting. Acid in sludge can cause burns.
7. Carefully lift the compressor (7) from the unit.