TM 9-4120-430-14
0015 00
WARNING
Do not use compressed air for cleaning purposes, except when reduced to less
than 30 psi (2.1 kg/cm2) and then only with effective chip guarding and
personal protective equipment.
Interval Column. Weekly and quarterly intervals are shown opposite the appropriate check. A weekly check is
performed weekly. If the check is accomplished quarterly, it is shown as a quarterly interval.
Table 1. Unit Preventive Maintenance Checks and Services (PMCS)
ITEM TO BE
EQUIPMENT NOT
ITEM
INTERVAL
CHECKED OR
PROCEDURE
READY/AVAILABLE
NO.
SERVICED
IF:
Figure 1. Evaporator Air Intake Louver PMCS
1
Weekly
Evaporator Air
1. See figure 1. Remove screws (1) and
Items are damaged,
Intake Filter and
washers (2) to release evaporator air
missing, or clogged.
Evaporator Air
intake louver (3) from unit (4). Remove
Intake Louver
air filter (5) and filter media (6) by
sliding filter out from either side of
louver casing.
2. Inspect air filter (5) and filter media (6)
for damage. Replace if damaged.
3. Clean air filter (5) and filter media (6)
with mild soap and water solution.
0015 00-2
|