TM 9-4120-430-14
0015 00
Table 1. Unit Preventive Maintenance Checks and Services (PMCS) - Continued
ITEM TO BE
EQUIPMENT NOT
ITEM
INTERVAL
CHECKED OR
PROCEDURE
READY/AVAILABLE
NO.
SERVICED
IF:
4. Inspect louver (3) for bent blades.
Straighten or replace.
5. Lubricate air filter (5) with filter-kote
(Item 17, WP 0069 00). Drain off
excessive oil.
6. Slide air filter (5) and filter media (6)
into attached clips of louver housing
(3).
7. Install evaporator air intake louver (3)
with screws (1) and washers (2).
2.
Weekly
Evaporator Air
1. See figure 2. Check louver (1) for dirt
Louver is missing or
Discharge Louver
or damage.
needs to be replaced.
2. Clean or replace damaged parts.
3. Inspect louver for bent blades.
Straighten or replace.
Figure 2. Evaporator Air Discharge Louver
3
Quarterly
Mist Eliminator
1. See figure 3. Remove top cover (1).
Items are damaged,
See WP 0018 00.
missing or clogged.
2. Slide mist eliminator (2) and filter
media (3) out of the mist eliminator
holder brackets (4 and 5).
3. Inspect mist eliminator (2) and filter
0015 00-3
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |