TM 9-4120-430-14
0015 00
Table 1. Unit Preventive Maintenance Checks and Services (PMCS) - Continued
ITEM TO BE
EQUIPMENT NOT
ITEM
INTERVAL
CHECKED OR
PROCEDURE
READY/AVAILABLE
NO.
SERVICED
IF:
media (3) for damage. Replace if
damaged.
4. Clean mist eliminator (2) and filter
media (3).
5. Install mist eliminator (2) and filter
media (3) in holder brackets (4 and 5).
Figure 3. Mist Eliminator
4
Quarterly
Evaporator and
1. Remove top cover (WP 0018 00) and
Items are loose or
Condenser Fans and
evaporator intake louver (WP 0020
damaged.
Motors
2. See Figure 4. Inspect evaporator motor
(1), condenser motor (2) and impellers
(3) and (4) for security of attachment,
rubbing and free turning.
3. Check wiring for damage.
0015 00-4
|