0015 00
Table 1. Unit Preventive Maintenance Checks and Services (PMCS) - Continued
ITEM TO BE
EQUIPMENT NOT
ITEM
INTERVAL
CHECKED OR
PROCEDURE
READY/AVAILABLE
NO.
SERVICED
IF:
Figure 7. Condensate Drains
8
Quarterly
Louver Actuator-
1. Remove top cover (WP 0018 00).
Condenser Discharge
Linear Assembly and
Louver and/or Fresh Air
Fresh Air Damper
Discharge Damper
Actuator Chain.
inoperative.
2. Check that the chain and Fresh Air
Damper operate smoothly and without
binding .
3. Check that linear actuator and
Condenser Discharge Louver operate
smoothly and without binding (requires
unit operation). Ensure the vanes of
the Condenser Discharge Louver are
angled outward and away from the
condenser coil, eliminating the
recirculation of heat.
4. Lubricate moving parts with small
amount of oil (Item 14, WP 0069 00).
5. Check for loose or missing mounting
hardware, bent louver or mechanical
parts.
9
Quarterly
Control Box
1. Pull out control box. Check for loose or
Disconnected wires,
disconnected wiring, cracks, or breaks.
loose or missing
hardware.
2. Check for loose or missing hardware.