TM 9-4120-430-14
0025 00
TEST
1. Position ventilation damper actuator chain (8) to fully closed position.
2. Shine flashlight into fresh air damper screen side of unit while looking into vent housing from compartment. Ensure
no light can be seen around edges of damper insulation seal. If test fails, service or replace ventilation damper as
necessary.
3. Install evaporator air intake louver (WP 0020 00).
END OF WORK PACKAGE