TM 9-4120-430-14
0028 00
REPLACEMENT
NOTE
Ensure wire leads are tagged before disconnecting.
Compressor Motor and Condenser Motor Relay (K1) (Figure 3)
1.
Remove the relay (K1) (1 ) from the junction box (4) by removing four screws (2) and lockwashers (3).
2
Install replacement relay (K1) (1) on the junction box chassis (4) with four lockwashers (3) and screws (2).
Heater Element Relays (K3 to K5), Evaporator and Condenser Motor Relay (K2)
1.
Remove the relays (K2-K5) (7) form the junction box (4) by removing two screws (5) and lockwashers (6) from
each relay.
2.
Install replacement relays (K2-K5) (7) on the junction box chassis (4).
3.
Secure each relay (7) to junction box chassis (4) with lockwashers (6) and two screws (5).
Compressor Time Delay Device (TD)
1.
Remove time delay device (TD) (11) from junction box chassis (4) by removing screw (8), lockwasher (9), and flat
washer (10).
2.
Install replacement time delay deice (TD) (11) on junction box chassis (4). Position as shown on exploded view.
3.
Secure time delay device to junction box with flat washer (10), lockwasher (9), and screw (8) removed in step 1
above.
Terminal Board (TB2) and Marker Strip
1.
Remove two screws (12) and lock nuts (13).
2.
Remove terminal board (TB2) (14) and marker strip (15) from junction box chassis (4).
3.
Install replacement terminal board (TB2) (14) and marker strip (15) on junction box chassis (4) using two screws
(12) and lock nuts (13).
Terminal Board (TB1) and Marker Strips
1.
Remove two lock nuts (16) and marker strip (17).
2.
Remove two lock nuts (18) and two screws (19) and remove terminal board (TB1) (20) and marker strip (21) from
side of junction box chassis (4).
3.
Install replacement marker strip (21) and terminal board (TB1) (20) on chassis (4) with two screws (19) and two
nuts (18).
4.
Install marker strip (17) over terminal board (TB1) (20) and secure with two lock nuts (16).
0028 00-7
|