TM 9-4120-430-14
UNIT MAINTENANCE
AIR CONDITIONER, COMPACT, HORIZONTAL
COIL (SOLENOID VALVE) MAINTENANCE
TEST, REMOVAL, AND INSTALLATION
INITIAL SETUP:
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0067 00)
Test Equipment
Multimeter
References
Wire list and Schematic Diagram (WP 0038 00)
Personnel Required
One
Equipment Condition
Power disconnected from unit.
Top cover removed (WP 0018 00).
.
WARNING
Ensure power source is disconnected.
TEST
1. Using multimeter set on the lowest OHMS scale, check for continuity between leads of coil. If continuity is not
found, coil is open and must be replaced.
2. Using multimeter set on lowest OHMS scale, check for continuity between each lead and coil casing. If continuity is
found between either lead and the casing, the coil is grounded and must be replaced.
REMOVAL
1. Tag and disconnect wires connected for solenoid valve coil (3). See figure 1.
2. Remove screw (1) and star washer (2).
3. Slide solenoid coil (3) off stem of solenoid valve (4).
INSTALLATION
1. Slide solenoid coil (3) onto valve stem of solenoid valve (4) and secure with star washer (2) and screw (1).
2. Refer to wire tags installed during removal and reconnect wires of coil as indicated and then remove tags.
3. Install top cover. See WP 0018 00.
4. Reconnect air conditioner to power source.