TM 9-4120-430-14
DIRECT SUPPORT MAINTENANCE
AIR CONDITIONER, COMPACT, HORIZONTAL
REFRIGERANT SYSTEM SERVICE - (PURGING)
INITIAL SETUP:
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0067 00)
Tool Kit, Service, Refrigeration Unit (Item 2, WP 0067 00)
Recovery and Recycle Unit, Refrigerant (Item 5, WP 0067 00)
Mask, Air Filtering (Item 29, Table 1, WP 0069 00)
Materials/Parts
Nitrogen (Item 4, WP 0069 00)
References
WP 0083 00 (MAC)
Personnel Required
One
Equipment Condition
Refrigerant system discharged (WP 0049 00)
Main power source is disconnected
WARNING
Ensure power source is disconnected.
WARNING
Be sure that the manifold hoses are correctly connected.
BLUE Hose = Low Pressure, RED Hose = High Pressure.
WARNING
The refrigeration system must be purged with dry nitrogen,
during any brazing operation performed on any component.
should be continued during all brazing operations to minimize internal oxidation and
scaling.
CAUTION
Nitrogen cylinders are pressurized containers. The pressure in the cylinder can
exceed 2000 psi. A nitrogen pressure regulator must be used at all times when
nitrogen is used for leak check or purge operations.
CAUTION
Nitrogen is an inert gas. However, it presents the danger of
asphyxiation and therefore, must be discharged in a
ventilated location.
0045 00-1
|