TM 9-4120-430-14
0050 00
6.
Compare gauge readings with the normal range of system pressure as shown on the Table of Normal Temperature.
Pressure Relationships.
7.
Disconnect gauges.
8.
Install service valve access cover with screws.
Table 1. Normal Temperature Pressure Relationships
Pressure Range (PSIG)
Temperatures
Outdoor Ambient
50 F (10 C)
75 F (24 C)
100 F (38 C)
120 F (52 C)
Evaporator Intake
90 F (32 C) Air to
55-65 Suction 150-
66-76 Suction 200-
76-86 Suction 280-
95-100 Suction 390-
Unit (Dry Bulb)
180 Discharge
240 Discharge
325 Discharge
428 Discharge
80 F (27 C) Air to
50-60 Suction 140-
61-71 Suction 190-
71-81 Suction 270-
80-90 Suction 360-
Unit (Dry Bulb)
170 Discharge
230 Discharge
315 Discharge
410 Discharge
Figure 1. Pressure Testing Setup
END OF WORK PACKAGE