Click here to make tpub.com your Home Page

Page Title: FILTER-DRIER LOCATION
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 9-4120-430-14
0051 00
FILTER-DRIER LOCATION
The filter-drier is located on the top center wall of the housing. See figure 1.
REMOVAL
WARNING
Ensure power source is disconnected.
Ensure the refrigerant system is discharged.
1.
Debraze refrigerant lines (1 and 2) from filter-drier (3) (WP 0046 00).
2.
Remove screw (4), lock nut (5), and strap (6).
3.
Remove filter-drier (3).
Figure 1. Filter-Dryer
INSTALLATION
CAUTION
Replacement filter-drier are packaged with sealing caps on the flare fittings to prevent
moisture contamination of the desiccant filtering media. Remove these caps immediately
prior to installation. Never install a filter-drier from which caps have been removed for an
extended or unknown period of time.
1.
Check the direction arrow marked on the filter-drier (3).
2.
Position filter-drier (3) between refrigerant lines (1 and 2).
0051 00-2