TM 9-4120-430-14
0059 00
WARNING
Ensure power source is disconnected.
WARNING
Compressor weighs as much as 92 lbs. (41.72 kg) and could cause injury to
personnel and damage to equipment if not handled properly while removing from
unit. Two personnel are required to lift the compressor.
CAUTION
When an overhead lifting device is used to remove the condenser fan supports (WP
0064 00), use an appropriate sling so that the weight of the unit is supported by the
base of the shipping container.
WARNING
Do not allow the unit to swing while suspended from a lifting device. Failure to
observe this warning may result in injury to personnel and damage to the equipment.
WARNING
Purge system with dry nitrogen prior to soldering or desoldering; refrigerant
heated by flame or hot surfaces creates phosgene gas, a highly toxic gas.
Do not let refrigerant touch you or inhale refrigerant gas. Be especially
careful to prevent refrigerant from coming in contact with your eyes. Use an
air filtering mask. In case of refrigerant leaks, ventilate area at once.
Follow general debrazing instructions given in WP 0051 00. Provide a flow
of dry nitrogen through the refrigeration system while debrazing
connections.
WARNING
Never operate compressor without the compressor terminal cover secured in place.
0059 00-2