TM 10-4110-262-13&P
0033 00
WARNING
Allow tubing to cool. Tubing is hot and can burn skin. Failure to comply
may result in serious injury to personnel.
CAUTION
Do not install the components until the tubing has cooled. Failure to
comply may result in damage to equipment.
5. Solder and connect the suction and discharge lines.
6. Reinstall the LPCO schrader valve core.
7. Reinstall the LPCO and HPCO.
8. Insulate the suction line.
9. Install the condenser support bracket.
10. Replace the dehydrator as described in WP 0037 00.
11. Pressurize the system and check for leaks.
12. Insert the wires disconnected from the old compressor into the compressor electrical box and connect
them to the appropriate terminals. Reinstall the cover.
13. Evacuate the system and recharge.
14. Perform system operation check in WP 0010 00.
15. Reinstall condenser front and top grilles and bottom panels.
END OF WORK PACKAGE