3-16. General
The air conditioner is constructed with removable
aluminum panels. The front access panel provides
access to the control box, control panel, and
charging valves. A discharge grille protects the
evaporator and mist eliminator and controls the
discharge of conditioned air. The intake grille pro-
tests the air conditioning filter and regulates the
amount of air returned to the unit. The condenser
coil grille and fan guard protects the condenser
coil and fan. A fresh air inlet screen permits the
entry of outside air and is controlled by the
damper door with the control spring and chain.
An intake cover provides for attachment of a
Chemical and Biological Filter Unit. The cover
panel covers the top of the unit.
Warning: Disconnect the air conditioner from
the power source before performing any mainte-
nance on the components of the unit.
3-17. Cover Panel, Discharge Grille, Intake
Grille, and Front Access Panel
a. Removal. Refer to figure 3-3 and remove the
cover panel, discharge grille, intake grille, and
front access panel.
b. Installation. Install the cover panel, discharge
grille, intake grille, and front access panel in re-
verse order of removal as illustrated on figure 3-3.
3-18. Mist Eliminator and Air Conditioning
Filter
a. Removal. Refer to figure 3-4 and remove the
mist eliminator and air conditioning filter.
b. Installation. Replace defective mist elimi-
nator and filter. Refer to figure 3-4 and install the
Figure 3-3. Cover panel, discharge grille, intake
mist eliminator and air conditioning filter in re-
grille, and front access panel, removal and installation.
verse removal order.
3-20. Evaporator Fan and Inlet Ring
3-19. Fresh Air Inlet Screen, Chemical and
Biological Cover, Fan Guard, and
a. General. New models of CE20VAL6 and
Condenser Coil Grille and Screen
CE20VAL4 air conditioner have air foil evapo-
rator fan. The air foil fan reduces excessive vibra-
a. Removal. Refer to figure 3-5 and remove the
fresh air inlet screen, C B (chemical and biolog-
tion and noise.
ical ) cover, fan guard, and condenser coil grille
b. Removal. Refer to figure 3-6 and remove the
and screen.
inlet ring and evaporator fan.
b. Installation. Install the fresh air inlet screen,
c. Installation. Install the inlet ring and evapo-
C B cover, fan guard, and condenser coil grille and
rator fan in reverse order of removal as illustrated
screen in reverse order of removal as illustrated