|
|
TM 5-4120-356-14
TABLE 4-1.2. pressure. Discharge and Suction Troubleshooting (cont.)
DISCHARGE
SUCTION
LOW
11. Check for plugged or kinked dis-
tributor tube.
12. Check for suction line or evaporator
coil tubing restriction.
13. Ensure dehydrator (filter-drier) is
not clogged.
14. Ensure there is no moisture in
refrigerant system.
WARNING
Disconnect the air conditioner from the electrical power source before at-
tempting to perform maintenance on the pressure switches.
a. High Pressure Cut-Out Switch
(1) Removal (See figure 4-8.)
(2) Test. (See figure 4-9.)
(3) Replace. Replace the high pressure cut-out switch if damage to the switch would impair serviceabil-
ity or if switch fails during test.
(4) Installation.
(a) Refer to figure 4-8 and install the high pressure cut-out switch in the unit.
(b) Perform any further maintenance of refrigeration system components required.
(c) Refer to paragraph 4-8 and purge the refrigerant system in accordance with the procedures given.
(d) Check the high pressure cut-out switch and the dehydrator for leaks in accordance with paragraph
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |