(7) I n s t a l l a t i o n .
(a) Refer to figure 4-12 and 4-20 and install the quench valve.
(b) Perform any further maintenance of refrigerant components re-
q u i r e d at this time.
(c) Reinstall the condenser fan (paragraph 3-15b).
(d) Purge the refrigerant system in accordance with the procedures
g i v e n in paragraph 4-8.
( e ) Check the quench valve and the dehydrator for leaks in accor-
d a n c e with paragraph 4-4c. If any leaks are found, repair in accordance with the
p r o c e d u r e s given in paragraph 4-4d.
(f) Refer to figure 4-4 and evacuate the refrigerant system.
( g ) Charge the system with refrigerant in accordance with the pro-
c e d u r e s given in paragraph 4-10.
1.
C o n d e n s e r Coil
(1) I n s p e c t i o n .
(a) Turn the selector switch to the "OFF" position and disconnect
the air conditioner from the electrical power source.
( b ) Remove the condenser fan (paragraph 3-15b).
( c ) Inspect the condenser coil for damage or defects which would
impair serviceability.
( d ) Check the condenser coil for leaks in accordance with the pro-
c e d u r e given in paragraph 4-4c.  R e p a i r any leaks found in accordance with the pro-
c e d u r e s given in paragraph 4-4d.
Replace the condenser coil if evidence of defects or dam-
(2) R e p l a c e .
a g e is found which would impair serviceability or if unrepairable leaks are found.
Refer to steps (3) and (4) for removal and installation of the condenser coil.
(3) R e m o v a l .
(a) Refer to figure 4-2 and release refrigerant from the system.
(b) Refer to figure 4-21 and remove the condenser coil,
(4) I n s t a l l a t i o n .
(a) Refer to figure 4-21 and install the condenser coil.
( b ) Perform any further maintenance of refrigerant components that
m a y be required at this time.