Table 5-1.
TROUBLESHOOTING-Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Check area near condenser guard and fresh air inlet
Step 5.
for heat hource over 120F (40C).
Remove heat source.
Check sight glass after operating unit for 15
Step 6.
minutes with TEMPERATURE SELECTOR switch in maximum
COOLER position.  Center should be bubble free and
green.
If charge is low add refrigerant.
(See para
Bubbles may also be caused by clogged
Use great care to avoid contact with liquid
refrigerant or refrigerant gas being
discharged from any container under pressure.
Sudden and irreversible tissue damage can
result from freezing.
Wear thermal protective gloves and a face
protector or safety glasses in any situation
where skin or eye contact is possible.
Prevent contact of refrigerant gas with flame
or hot metal surfaces.
Heat causes the refrigerant to break down and
form carbonyl chloride (phosgene), a highly
toxic and corrosive gas.
Check for refrigerant leaks.
Step 7.
Repair or change defective part.
High voltage can kill.
Check solenoid valves L1 and L2.
Step 8.
Repair or replace if defective.
5-8