TM5-4120-383-14
Table 5-1.
TROUBLESHOOTING-Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
(See para 5-24.)
Check pressure regulator valve.
Step 9.
Replace if defective.
(See
Step 10. Check expansion valve for proper operation.
Replace if defective.
(See para
Step 11. Check quench valve for proper operation.
Replace if defective.
REFRIGERANT SYSTEM CONTINUOUSLY LOSING REFRIGERANT
4.
Use great care to avoid contact with liquid
refrigerant or refrigerant gas being
discharged from any container under pressure.
Sudden and irreversible tissue damage can
result from freezing.
Wear thermal protective gloves and a face
protector or safety glasses in any situation
where skin or eye contact is possible.
Prevent contact of refrigerant gas with flame
or hot metal surfaces.
Heat causes the refrigerant to break down and
form carbonyl chloride (phosgene), a highly
toxic and corrosive gas.
Check refrigerant tubing and components for leaks
Step 1.
(See para 5-14.)
using a leak detector.
Repair or replace as required.
(See para 5-28.)
Check pressure relief valve.
Step 2.
Replace if defective.
5-9
|