TM5-4120-384-14
4-4.
INSTALLATION
INSTRUCTIONS.-Continued
(7) Remove the condensate drain plug from lower left rear
If air conditioner is mounted in a location
corner of the unit.
where water pouring from this drain will be objectionable or create
The fitting used
a hazard, connect a drain line at this point.
Hose, rigid pipe
must have a male 1/8 - 27 NPT connection to unit.
or tubing can be used to direct drain water to a more desirable
disposal location.
(8) Connect
power
cable
to
proper
input
power
source
and
air
conditioner.
(9)
Run
operational
checks
in
accordance
with
4-5. PRELIMINARY SERVICING AND ADJUSTMENT OF EQUIPMENT.
Lubrication.
a.
General.
The refrigerant compressor and its drive motor are
hermetically sealed in a canister.
The compressor is supplied with
The
a complete charge of oil and requires no lubrication.
evaporator and condenser fan motors also have permanently
lubricated, sealed bearings.
No lubrication of these items is
required.
The only mechanical items which may
Mechanical Lubrication.
b.
require lubrication are the conditioned air supply and return
and the devices which operate the fresh air damper door.
These
points should be checked and lubricated, as necessary, during
A few drops of light oil should be
preventive maintenance service.
applied to pivot points, bearing surfaces, and linkages to prevent
Be sure to wipe off all excess
or eliminate stiffness or binding.
These items are in an area of
oil with a cloth or paper towel.
high volume airflow and excess oil will tend to attract and
Graphite may be
accumulate dust particles from the passing air.
used as an alternate lubricant during extreme cold weather
operation.
Change 2
4-19
|