TM5-4120-384-14
5-2.
USE OF TROUBLESHOOTING TABLE.-Continued
WARNING
Use  great  care  to  avoid  contact  with  liquid
refrigerant  or  refrigerant  gas  being  discharged  from
Sudden and
any  container  under  pressure.
irreversible  tissue  damage  can  result  from  freezing.
Wear  thermal  protective  gloves  and  a  face  protector
or  safety  glasses  in  any  situation  where  skin  or  eye
contact  is  possible.
Prevent  contact
of
refrigerant
gas
with
flame
or
hot
metal  surfaces.
Heat  causes  the  refrigerant  to  break  down  and  form
carbonyl  chloride  (phosgene),  a  highly  toxic  and
corrosive  gas.
TROUBLESHOOTING
Table
5-1.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
High
voltage
can
kill.
1.
COMPRESSOR WILL NOT START.
NOTE
Be sure and check Item 1, Steps 1 through 6,
Table  4-2  Troubleshooting  for  organizational
maintenance  before  proceeding  with  Step  1.
Step
1.
Check that the COMPR CIRCUIT BKR is ON.
Reset  to  ON  position.
If  circuit  breaker  will
not  remain  ON,  check  and/or  replace.
(See  para
5-4