TROUBLESHOOTING-Continued
Table
5-1.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step
5.
Check  area  near  condenser  guard  and
fresh
air
inlet
for heat hource over 120F (40C).
Remove
heat
source.
Step
6.
Check  sight  glass  after  operating  unit  for  15
m i n u t e s with TEMPERATURE SELECTOR switch in maximum
COOLER  position.
Center  should  be  bubble  free  and
green.
If  charge  is  low  add  refrigerant.
(See  para
Bubbles may also be caused by clogged
Use  great  care  to  avoid  contact  with  liquid
refrigerant  or  refrigerant  gas  being
discharged  from  any  container  under  pressure.
Sudden  and  irreversible  tissue  damage  can
result  from  freezing.
Wear  thermal  protective  gloves  and  a  face
protector  or  safety  glasses  in  any  situation
where  skin  or  eye  contact  is  possible.
Prevent  contact  of  refrigerant
gas
with
flame
or  hot  metal  surfaces.
Heat  causes  the  refrigerant  to  break  down  and
form  carbonyl  chloride  (phosgene),  a  highly
toxic  and  corrosive  gas.
(See
Check
for
refrigerant
leaks.
Step
7.
Repair
or
change
defective
part.
High
voltage
can
kill.
Step
8.
(See
Check solenoid valves L1 and L2.
Repair
or
replace
if
defective.
5-8