5 - 2 2 . EXPANSION VALUE (PRIMARY).
The (primary) expansion valve is factory set at a superheat temperature of
6 1/2F (3.3 0.3C) at 32F (0C) bath temperature. Do not attempt field
adjustment of the valve.
(See
a.
Removal.
(1)
Disconnect
power
at
power
source.
(2)  (Models  F18H-3S  and  F18H-lS)  Remove  three  top  covers
(Models  F18H-3SA  and  F18H-3SB)  Remove  top  cover  (para
(3)  Discharge
and
purge
refrigeration
system
per
and  5-12.
(4)
Unwrap
insulation
from
joints
of
expansion
valve.
(5)  Soften  thermal  mastic  in  the  bulb  well  using  a  cloth
wrung out in hot water, a heat lamp,  or  heat  gun  if  necessary  and
withdraw  bulb  from  bulb  well.
(6)
Debraze
two
tube
connections
and
restrictor
connection
to
valve.
(7)
Remove
valve
from
unit.
Replace.
If
expansion
valve
is
suspected
bad
replace
it.
b.
Installation.
c.
(1)
Place
expansion
valve
in
unit
and
align
tubing
ends.
(2)  Protect  valve  from
overheating  during  brazing  operations.
Direct  flame  away  from  valve
body  and  wrap  valve  body  with  wet
rags.
(3)
Braze
joints
in
accordance
with
(4)
Replace
(See
(5)  Leak  test  all  newly  connected  joints
and
all
tube
connections  in  the  area.
(6)
Rewrap
insulation
at
expansion
valve
joints.
(7)
Install
sensing
bulb
in
bulb
well.
Insert  approximately
one
ounce
of
thermal
mastic
in
(a)
bulb  well.
Change 2