TM 5-4120-386-14
Table 4-2. Organizational Troubleshooting - Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
3. EVAPORATOR OR CONDENSER FAN MOTOR FAILS TO OPERATE - Continued
Step 5.
24 volt DC source, then check continuity of contacts that should be
closed.
Replace bad relay. (Refer to paragraph 4-25.)
Inspect for bad evaporator fan speed control switch by checking
Step 6.
continuity with ohmmeter.
Replace bad switch. (Refer to paragraph 4-24.)
Inspect mode selector Rotary switch for improper adjustment of
Step 7.
damper.
Replace bad switch. (Refer to paragraph 4-24.)
4. COMPRESSOR WILL NOT START
Disconnect the power source before performing any troubleshooting function.
Make sure that compressor or control circuit breakers or selector
Step 1.
switch is properly set.
Make continuity check of control circuit to determine whether open
Step 2.
circuit exists.
Repair open circuit or replace wire.
(Refer to Wiring Diagram E-1.)
Step 3. Check continuity across primary winding and across secondary winding
of control transformer to see whether windings are good.
Replace bad transformer. (Refer to paragraph 4-29.)
Step 4. Apply 30 volts AC across side input terminals; check for 24-28 volts DC
across output terminals (marked + and -) of rectifier.
Replace bad rectifier. (Refer to paragraph 4-28.)