5-18. Liquid Indicator
This task covers:
a. Inspection
c. Installation
b. Removal
Initial setup.
Tools:
Tool kit, service, refrigeration unit NSN 5180-00-596-1474
Personnel: 1
Equipment condition:
1. Turn unit power off at power source. If there is a chance that it will be turned on, also disconnect power
cable to air conditioner.
2. Remove lower front panel. See para 4-24.
General Safety Instructions:
WARNING
Disconnect input power to the air conditioner before performing any internal
maintenance. Voltages used can KILL. Shutting the unit off at the control panel
does not disconnect unit power.
INSPECTION
1.
Check that glass window is clean and not cracked or broken. Clean if dirty. Replace liquid indicator if cracked or
broken.
2.
Check for evidence of leakage. Leak test if leak is suspected. See para 5-12. Repair or replace as indicated.
REMOVAL
1.
Using screwdriver, remove two screws (1) and washers (2) from rear while holding bracket (3) so that it does not drop
down into unit.
2.
Remove bracket (3).
3.
Discharge refrigerant system. See para 5-9.
4.
5.
Remove liquid indicator (4).
5-41
|