Click here to make tpub.com your Home Page

Page Title: DESCRIPTION AND USE OF CONTROLS AND INDICATORS
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 9-4120-425-14&P
DESCRIPTION AND USE OF CONTROLS AND INDICATORS
GENERAL
The air conditioner is a self-contained and electric powered unit that provides 36,000 BTU/HR for cooling or 31,200
BTU/HR for heating. Once started, it operates automatically due to the relationship of the components, controls and
instruments.
The air conditioner is designed for a variety of installations and for operation under a wide range of climactic conditions.
It is also designed for continuous or intermittent operation as a self-contained unit. Operators must be aware of any
peculiarities or operational limitations for their specific installation. See the appropriate shelter or system manual for
instructions peculiar to your specific installation.
The air conditioner is not equipped with a CBR filter, however, the unit could be connected to external filtering
equipment for operation under CBR environmental conditions.
OPERATOR'S CONTROLS
1. Cooling
With the MODE SELECTOR switch in COOL position, the fan motor is energized. The fan motor runs continuously.
The temperature selector switch determines the cooling mode of unit. With the temperature selector switch calling for
compressor operation, the liquid line solenoid valve opens and closes with the electronic thermostat switch to control the
flow within the refrigerant circuit. The air conditioner is protected from current overload by a circuit breaker in the
control module and a thermal overload in the compressor terminal cover.
2. Heating
With the MODE SELECTOR switch in the HEAT position, air is blown by the evaporator fan as in cooling, but the
heating elements are energized instead of the refrigeration system.
3. Ventilation
Placing the MODE SELECTOR switch in the VENT position energizes the evaporator fan motor which forces air out of
the evaporator discharge louver into the room. The amount of outdoor air used for ventilation is determined by the
position of the ventilation damper door.
0005-00-1

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business