CONDENSER FAN SCROLLS DIRECT SUPPORT MAINTENANCE
0063-00
REPLACEMENT - Continued
REMOVAL Con tinued
5.
Remove condenser motor brace (29) from condenser support (32) by removing four screws (30) and four lock
washers (31). See Figure 2.
NOTE
Mounting parts (screws, washers and brackets) are the same for each scroll (5 and 6).
Disassembly is also the same for each scroll.
Remove two screws (2), two flat washers (3), and two grommets (4) from scroll (5). See Figure 1.
6.
7.
Remove two screws (7), two flat washers (8), two nonmetallic grommets (9), and spacers (10 and 11) to release
scroll (5) from scroll support (12). Leave scroll support in place unless damaged, then replace.
8.
Carefully move back service valve piping and lift out scroll from unit housing.
9.
Repeat for other condenser fan scroll (6) as required.
INSTALLATION
1.
If removed, install scroll support (12) with two screws (13), two flat washers (14) and two nuts (15). See figure 1.
2.
Position spacers (10 and 11), two grommets (9) and scroll (5) onto scroll support (12) and secure with two screws
(7) and two flat washers (8).
3.
Install two grommets (4), two flat washers (3) and two screws (2).
Install condenser motor brace (29) with four screws (30) and four lockwashers (31). See Figure 2.
4.
5.
Install motor mounting bracket (22) with two screws (23), two lockwashers (24), one screw (25), one screw (26),
one lockwasher (27), and six screws (28).
6.
Repeat steps (1 thru 5) for right hand scroll (6). See figure 1.
7.
Install actuator mounting bracket and damper actuator cylinder subassembly (16) with four screws (17), and lock
washers (18). See igure 2.
8.
Install condenser fan motors. See WP 0062-00.
9.
Secure service valve clamps to scroll (5). See WP 0073-00.
10. Install louver actuator cables (1). See WP 0032-00.
11. Install liquid sight mounting hardware. See WP 0075-00.
12. Install condenser air discharge louvers. See WP 0021-00.
13. Install top panels. See WP 0019-00.