TM 9-4120-425-14&P
CONDENSER FAN SCROLLS DIRECT SUPPORT MAINTENANCE REPLACEMENT
THIS WORK PACKAGE COVERS:
Removal and Installation
INITIAL SETUP:
Maintenance Level
Direct Support
Tools and Special Tools
Tool Kit, General Mechanics (Item 1, Table 2, WP 0118-00)
Equipment Condition
Main power source is disconnected, shut down and cool.
Top panel removed (WP 0019-00).
Liquid sight indicator mounting hardware removed (WP 0075-00).
Louver actuator cables removed (WP 0032-00).
Condenser fan motors removed (WP 0062-00).
Condenser air discharge louvers removed (WP 0021-00).
Service valve clamps disassembled from scrolls (WP 0073-00).
WARNING
Disconnect air conditioner power input connector before doing maintenance work on
electrical system.
NOTE
The following are removal and installation instructions for scroll (5). Instructions for
scroll (6) are similar except it does not have service valve clamp attachment.
REMOVAL
Remove louver actuator cables (1) (figure 1) from unit. Refer to WP 0032-00 for instruction on removal of cables and
1.
replacement of defective/damaged components.
NOTE
When performing steps 2 and 3 do not break in the refrigerant system or loosen
refrigerant connections.
2.
Remove actuator mounting bracket and damper actuator cylinder subassembly (16) from motor mounting brackets
(21) and (22) by removing four screws (17) and four lockwashers (18). Carefully move the subassembly (16) away
from the motor mounting bracket. See Figure 2.
3.
Release service valve clamps from left hand scroll (5) and carefully move refrigerant tubing away from condenser
fan scroll mounting area. See WP 0073-00.
4.
Remove motor mounting bracket (22) by removing two screws (23), two lock washers (24), one screw (25), one
screw (26), one lock washer (27), and six screws (28). See Figure 2.
0063-01-1
|