TM 9-4120-425-14&P
LIQUID SIGHT INDICATOR
DIRECT SUPPORT MAINTENANCE REPLACEMENT - Continued
0075-00
WARNING
Check that power source is disconnected. Check that refrigerant system is discharged.
REMOVAL
1.
Remove screw (1), washer (2) and mounting plate (3) to release the liquid sight indicator (4) from side of housing.
2.
With a steady flow of dry nitrogen through refrigeration system, debraze liquid sight indicator from condenser coil
and attached tubing (See WP 0050-00 and WP 0051-00).
0075-00-2
|